WP-C40 Universal Display Controller is widely applicable for pressure, level and temperature control solution as secondary instrument providing display, output signal conversion, alarm and other functions for measuring devices. Two panel screens on separately display primary measured reading(PV) and secondary information(SV). Integrated up to 4 relay switches provide HH, H, L and LL alarms. Relay state can be set between normally open & close.
|
Item name |
WP Series Dual Screen Smart Display Controller |
|
|
Model |
Size (mm) |
Panel cutout |
|
WP-C10 |
48*48*108 |
44+0.5 * 44+0.5 |
|
WP-S40 |
48*96*112(Vertical type) |
44+0.5 * 92+0.7 |
|
WP-C40 |
96*48*112(Horizontal type) |
92+0.7 * 44+0.5 |
|
WP-C70 |
72*72*112 |
67+0.7 * 67+0.7 |
|
WP-C90 |
96*96*112 |
92+0.7 * 92+0.7 |
|
WP-S80 |
80*160*80(Vertical type) |
76+0.7 * 152+0.8 |
|
WP-C80 |
160*80*80(Horizontal type) |
152+0.8 * 76+0.7 |
|
Code |
Input signal |
Display range |
|
00 |
K thermocouple |
0~1300℃ |
|
01 |
E thermocouple |
0~900℃ |
|
02 |
S thermocouple |
0~1600℃ |
|
03 |
B thermocouple |
300~1800℃ |
|
04 |
J thermocouple |
0~1000℃ |
|
05 |
T thermocouple |
0~400℃ |
|
06 |
R thermocouple |
0~1600℃ |
|
07 |
N thermocouple |
0~1300℃ |
|
10 |
0-20mV |
-1999~9999 |
|
11 |
0-75mV |
-1999~9999 |
|
12 |
0-100mV |
-1999~9999 |
|
13 |
0-5V |
-1999~9999 |
|
14 |
1-5V |
-1999~9999 |
|
15 |
0-10mA |
-1999~9999 |
|
17 |
4-20mA |
-1999~9999 |
|
20 |
RTD Pt100 |
-199.9~600.0℃ |
|
21 |
RTD Cu100 |
-50.0~150.0℃ |
|
22 |
RTD Cu50 |
-50.0~150.0℃ |
|
23 |
BA2 |
-199.9~600.0℃ |
|
24 |
BA1 |
-199.9~600.0℃ |
|
27 |
0-400Ω |
-1999~9999 |
|
28 |
WRe5-WRe26 |
0~2300℃ |
|
29 |
WRe3-WRe25 |
0~2300℃ |
|
31 |
0-10mA square root |
-1999~9999 |
|
32 |
0-20mA square root |
-1999~9999 |
|
33 |
4-20mA square root |
-1999~9999 |
|
34 |
0-5V square root |
-1999~9999 |
|
35 |
1-5V square root |
-1999~9999 |
|
36 |
Customized input |
|
Code |
Current output |
Voltage output |
Transmit range |
|
00 |
4~20mA |
1~5V |
-1999~9999
|
|
01 |
0~10mA |
0~5V |
|
|
02 |
0~20mA |
0~10V |
|
|
Note: WP-C10 can have no more than 2 relays and no output. WP-C80/S80 can have up to 6 relays. For more information about intelligent indicators please feel free to contact us. |
|||